Bộ Nguồn 6EP1336-2BA10 / SITOP PSU100S 24 V/20 A
SITOP PSU100S 20 A Stabilized power supply input: 120/230 V AC,
output: 24 V DC/20 A
Input
| Input | 1-phase AC |
| ● Note | Automatic range selection |
| Supply voltage | |
| ● 1 at AC Rated value | 120 V |
| ● 2 at AC Rated value | 230 V |
| Input voltage | |
| ● 1 at AC | 85 … 132 V |
| ● 2 at AC | 176 … 264 V |
| Wide-range input | No |
| Overvoltage resistance | 2.3 × Vin rated, 1.3 ms |
| Mains buffering | at Vin = 120/230 V |
| Mains buffering at Iout rated, min. | 20 ms; at Vin = 120/230 V |
| Rated line frequency 1 | 50 Hz |
| Rated line frequency 2 | 60 Hz |
| Rated line range | 47 … 63 Hz |
| Input current | |
| ● at rated input voltage 120 V | 7.5 A |
| ● at rated input voltage 230 V | 3.5 A |
| Switch-on current limiting (+25 °C), max. | 11 A |
| I²t, max. | 10 A²·s |
| Built-in incoming fuse | T 10 A (not accessible) |
| Protection in the mains power input (IEC 898) | Recommended miniature circuit breaker: from 10 A characteristic C or circuit-breaker 3RV2411-1JA10 (120 V) or 3RV2411-1FA10 (230 V) |
Output
| Output | Controlled, isolated DC voltage |
| Rated voltage Vout DC | 24 V |
| Total tolerance, static ± | 3 % |
| Static mains compensation, approx. | 0.5 % |
| Static load balancing, approx. | 1 % |
| Residual ripple peak-peak, max. | 150 mV |
| Spikes peak-peak, max. (bandwidth: 20 MHz) | 240 mV |
| Adjustment range | 24 … 28 V |
| Product function Output voltage adjustable | Yes |
| Output voltage setting | via potentiometer; max. 480 W |
| Status display | Green LED for 24 V OK |
| Signaling | Relay contact (NO contact, rating 50 V DC/ 0.3 A) for “24 V OK” |
| On/off behavior | No overshoot of Vout (soft start) |
| Startup delay, max. | 1.5 s |
| Voltage rise, typ. | 50 ms |
| Voltage increase time of the output voltage maximum | 500 ms |
| Rated current value Iout rated | 20 A |
| Current range | 0 … 20 A |
| ● Note | 24 A up to +45°C; +60 … +70 °C: Derating 5%/K |
| Supplied active power typical | 480 W |
| Short-term overload current | |
| ● on short-circuiting during the start-up typical | 35 A |
| ● at short-circuit during operation typical | 35 A |
| Duration of overloading capability for excess current | |
| ● on short-circuiting during the start-up | 100 ms |
| ● at short-circuit during operation | 100 ms |
| Parallel switching for enhanced performance | Yes |
| Numbers of parallel switchable units for enhanced performance |
2 |