SMART TRANSMITTER POWER SUPPLY KCD2-STC-1.SP
TÍNH NĂNG NỔI BẬT
- Bộ điều hòa tín hiệu 1 kênh
- Nguồn cung cấp 24 V DC (Đường ray điện)
- Đầu vào cho máy phát SMART 2 dây và nguồn hiện tại
- Đầu ra cho 4 mA … 20 mA hoặc 1 V … 5 V
- Vỏ rộng 12,5 mm
- Kết nối qua thiết bị đầu cuối lò xo với công nghệ kết nối đẩy vào
- Up to SIL 2 acc. to IEC/EN 61508
THÔNG SỐ KỸ THUẬT
General specifications | ||
---|---|---|
Signal type | Analog input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 9+, 10- | |
Rated voltage | 19 … 30 V DC | |
Ripple | ≤ 10 % | |
Rated current | ≤ 45 mA at 24 V and 20 mA source mode output | |
Power dissipation | ≤ 800 mW | |
Power consumption | ≤ 1.1 W | |
Input | ||
Connection side | field side | |
Connection | terminals 1+, 2-; 3+, 4- | |
Input signal | 4 … 20 mA limited to approx. 26 mA | |
Open circuit voltage/short-circuit current | terminals 1+, 2-: 20 V / 26 mA | |
Voltage drop | terminals 3+, 4- : approx. 5 V | |
Available voltage | terminals 1+, 2-: ≥ 16 V at 20 mA ; ≥ 17 V at 4 mA | |
Output | ||
Connection side | control side | |
Connection | terminals 5-, 6+ terminals 5-, 8+ for HART resistor |
|
Load | 0 … 525 Ω (10.5 Vmax source mode) | |
Output signal | 4 … 20 mA or 1 … 5 V (on 250 Ω, 0.1 % internal shunt) 4 … 20 mA (sink mode), operating voltage 5 … 30 V |
|
Ripple | 20 mV rms | |
Transfer characteristics | ||
Deviation | at 20 °C (68 °F) < 0.1 % of full scale, incl. non-linearity and hysteresis (source mode and sink mode 4 … 20 mA) ≤ ± 0.2 % incl. non-linearity and hysteresis (source mode 1 … 5 V) |
|
Influence of ambient temperature | < 2 µA/K (-20 … 70 °C (-4 … 158 °F)); < 4 µA/K (-40 … -20 °C (-40 … -4 °F)) (source mode and sink mode 4 … 20mA) < 0.5 mV/K (-20 … 70 °C (-4 … 158 °F)); < 1 mV/K (-40 … -20 °C (-40 … -4 °F)) (source mode 1…5 V) |
|
Frequency range | field side into the control side: bandwidth with 0.5 Vpp signal 0 … 3 kHz (-3 dB) control side into the field side: bandwidth with 0.5 Vpp signal 0 … 3 kHz (-3 dB) |
|
Settling time | ≤ 50 ms | |
Rise time/fall time | ≤ 10 ms | |
Galvanic isolation | ||
Input/Output | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Input/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Output/power supply | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Indicators/settings | ||
Display elements | LED | |
Control elements | DIP switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2017 EN 61326-3-2:2018 |
|
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -40 … 70 °C (-40 … 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | spring terminals | |
Mass | approx. 100 g | |
Dimensions | 12.5 x 119 x 114 mm (0.5 x 4.7 x 4.5 inch) (W x H x D) , housing type A2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |